Range of product | Telemecanique Pressure sensors XM |
---|---|
Product or component type | Electronic pressure sensors |
Pressure sensor type | Pressure transmitter |
Pressure switch type of operation | Pressure transmitter with 1 switching output |
Device short name | XMLR |
Pressure rating | 160 bar 15995.84 kPa |
Maximum permissible accidental pressure | 47987.51 kPa 480 bar 48 MPa |
Destruction pressure | 960 bar 96 MPa 95975.02 kPa |
Controlled fluid | Fresh water (0…80 °C) Air (-20…80 °C) Hydraulic oil (-20…80 °C) Refrigeration fluid (-20…80 °C) |
Fluid connection type | G 1/4 (female) conforming to DIN 3852-Y |
[Us] rated supply voltage | 24 V DC SELV (voltage limits: 17…33 V) |
Current consumption | <= 50 mA |
---|---|
Electrical connection | Male connector M12, 4 pins |
Analogue output function | 4...20 mA |
type of output signal | Analogue + discrete |
Analogue output function | 4...20 mA |
Discrete output type | Solid state PNP, NO/NC programmable |
Maximum switching current | 250 mA |
Contacts type and composition | NO/NC programmable |
Scale type | Fixed differential |
Maximum voltage drop | 2 V |
Adjustable range of switching point on rising pressure | 1.28…16 MPa 1282.42…15995.84 kPa 12.8…160 bar |
Adjustable range of switching point on falling pressure | 8…155 bar 799.79…15513.20 kPa 0.8…15.5 MPa |
Minimum differential travel | 0.48 MPa 479.88 kPa 4.8 bar |
materials in contact with fluid | 316L stainless steel |
Front material | Polyester |
Housing material | Polyacrylamide 316L stainless steel |
Operating position | Any position, but disposals can falsified the measurement in case of upside down mounting |
Protection type | Overload protection Overvoltage protection Reverse polarity Short-circuit protection |
Response time on output | <= 10 ms for analog output <= 5 ms for discrete output |
switching output time delay | 0...50 s in steps of 1 second |
Display type | 4 digits 7 segments |
Local signalling | 1 LED (yellow) for light ON when switch is actuated |
Display response time type | Fast 50 ms Normal 200 ms Slow 600 ms |
Maximum delay first up | 300 ms |
overall accuracy | <= 1 % of the measuring range |
linearity error on analogue output | <= 0.5 % of the measuring range |
hysteresis on analogue output | <= 0.2 % of the measuring range |
measurement accuracy on switching output | <= 0.6 % of the measuring range |
Repeat accuracy | <= 0.2 % of the measuring range |
Drift of the sensitivity | +/- 0.03 % of measuring range/°C |
Drift of the zero point | +/- 0.1 % of measuring range/°C |
Display accuracy | <= 1 % of the measuring range |
Mechanical durability | 10000000 cycles |
Depth | 42 mm |
Height | 88 mm |
Width | 41 mm |
Net weight | 0.186 kg |
[Uimp] rated impulse withstand voltage | 0.5 kV DC |
Electromagnetic compatibility | Susceptibility to electromagnetic fields: 10 V/m 80...2000 MHz conforming to EN/IEC 61000-4-3 Immunity to conducted RF disturbances: 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6 Surge immunity test: 1 kV conforming to EN/IEC 61000-4-5 Electrical fast transient/burst immunity test: 2 kV conforming to EN/IEC 61000-4-4 Electrostatic discharge immunity test: 8 kV air, 4 kV contact conforming to EN/IEC 61000-4-2 |
Marking | CE |
---|---|
Product certifications | CULus EAC |
Standards | UL 61010-1 EN/IEC 61326-2-3 |
Ambient air temperature for operation | -20…80 °C |
Ambient air temperature for storage | -40…80 °C |
IP degree of protection | IP65 conforming to EN/IEC 60529 IP67 conforming to EN/IEC 60529 |
Vibration resistance | 20 gn (f= 10…2000 Hz) conforming to EN/IEC 60068-2-6 |
Shock resistance | 50 gn conforming to EN/IEC 60068-2-27 |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |